• 8 universal analog input channels:
Thermocouples, V, mV, mA, Pt100 and Pt1000
Channel reading and recording rates of up to 1000/second
24-bit A/D conversion resolution
• 8 digital I/Os (individually configured as input or output)
• 2 relay outputs (NO, NC and common)
• RS485 interface (Modbus master or slave)
When acting as a master, it can read up to 64 registers from other slaves
The read registers can be used in logging, alarms or mathematical operations
• Ethernet interface with several services available
Sending of alarm alerts by e-mail (SMTP)
Provides web pages with channels and status information (HTTP); Allows downloading of recorded data via FTP (client and server)
Accesses status and channel values via network management software (SNMP and traps)
Allows Modbus communication via Ethernet interface (Modbus TCP)
• USB-device interface for configuration, monitoring and collection
• USB-host interface for data collection via pen drive
• Up to 32 configurable alarms:
Alarm actions may include: programming periodic alarms for accumulator reset, activating relays, activating digital outputs, sending e-mails to multiple receivers, sending SNMP traps, starting and/or stopping logging
• Up to 128 virtual channels:
Mathematical functions to be applied to other channels: addition, subtraction, multiplication, division, rooting, exponentiation, sine, cosine, logic (AND, OR and exclusive OR), square root and power
• 24 Vdc auxiliary power supply for powering up to 8 4-20 mA transmitters
• Power supply:
Power AC (100 to 240 V AC)
DC (12 to 30 V DC) power optional (2011)
• Detachable QVGA HMI (optional)
Keypad and color QVGA TFT display
RS485 communication with FieldLogger
• FDA CFR21 Part 11 compliant
Configurable via NXperience Trust software.
• Logging
Up to 100 channels can be logged at a configurable rate
Data download via the configuration software or via the freely distributed download DLL
• UL and CE listed

Bộ thu thập dữ liệu Datalogger NOVUS FieldLogger RS485